7
Technical Specifications
Table 7-1 Key technical specifications
Item
Specifications
Module dimensions (H x W x D)
(mm)
Fully enclosed indoor cabinet: 2000 x
600 x 1350
Number of cabinets
1 PCS
Power system
220 V/230 V/240 V, 1 Ph, 50 Hz/60 Hz
Voltage range
220–240 V
Voltage frequency range
50/60 Hz (± 3 Hz)
Maximum power of a single cabinet
≤ 3 kW
IP rating
IP20
Altitude
0–4000 m (derated when the altitude
exceeds 1000 m)
Installation mode
Installed on a concrete floor or an ESD
floor
Cable and pipe routing
● Pipes are routed from the top or
bottom.
● Input power cables of the cabinet can
be routed in from the top or bottom,
and other power cables can be routed
out from the top.
● Signal cables can be routed out from
the top or bottom.
Operating temperature
Indoor: 0–40°C
Outdoor: –20°C to +45°C
Storage temperature
–40°C to +70°C
Storage humidity
≤ 95% RH (non-condensing)
FusionModule500 Smart Mini Data Center
User Manual
7 Technical Specifications
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
289