3.1 Structural System
The cabinet possesses the following features:
●
The cabinet houses standard 19-inch wide devices.
●
Half-height rPDUs can be vertically installed at the rear of the cabinet.
●
The position of each U is marked on the vertical mounting bars.
●
The front and rear doors of the cabinet can be locked, and can be unlocked
by using dedicated keys.
●
The cabinet can be installed on a base (which needs to be prepared by
customers).
●
The cabinet can house ICT devices with a depth of no more than 750 mm.
Table 3-1 Cabinet technical specifications
Item
Specifications
Color
Black
Material
High-intensity class A carbon cold rolled steel
plate and zinc-coated steel plate
Air channel
Cold aisle containment
Installation mode
Installed on a concrete floor or electrostatic
discharge (ESD) floor
Static load
1500 kg
Dynamic load
1000 kg
IP rating
IP20
FusionModule500 Smart Mini Data Center
User Manual
3 System Architecture
Issue 02 (2020-12-25)