3.4.2.1 Monitoring
●
Temperature and humidity monitoring: Detects and collects statistics on the
ambient temperature and humidity inside the smart module.
●
Water leakage monitoring: Detects water leakage at the bottom of the smart
module and provides real-time alarm signals.
●
Smoke monitoring: Detects smoke in the smart module and provides real-
time alarm signals.
●
Power distribution monitoring:
a. (In the intelligent power distribution scenario) Monitors the general
mains input voltage, frequency, current, and power, as well as the UPS
input voltage, frequency, current, and so on.
b. (In the non-intelligent power distribution scenarios) Monitors the UPS
input voltage, frequency, current, and so on.
●
Smart cooling product monitoring:
a. Configures the supply air temperature set point in a unified manner,
without the need to separately configure it for each smart cooling
product.
b. Monitors and displays the fan speed, and displays the running
percentage.
c.
Displays the cooling load rate.
d. Monitors and displays the compressor running status.
e. Displays the real-time running status of the heating and humidifying.
●
Video surveillance: Connects to three cameras and provides PoE power supply;
accesses real-time video images on the WebUI and invokes historical
monitoring data.
3.4.2.2 App View
●
Generates a 2.5D layout view that matches the actual layout of the smart
module, including the power distribution module, smart cooling product, and
T/H sensor. In addition, the resource usage rate of electric energy (displayed
only when the intelligent power distribution module is configured), ambient
temperature and humidity of the smart module are displayed on the home
screen of the app.
●
Displays the resource usage of the electric energy of the smart module and
each cabinet (displayed only when the intelligent power distribution module
is configured).
●
Displays the real-time status and alarms of the aisle temperature and
humidity sensor in the plan view.
●
After logging in to the app installed on the PAD, you can open the cabinet
door on the corresponding screen.
3.4.2.3 Alarm
●
The system monitors the status of smart cooling products, power distribution,
and environment. If a fault or parameter error occurs, the system generates
an alarm in real time. You can view the alarm cause and solution in the alarm
details.
FusionModule500 Smart Mini Data Center
User Manual
3 System Architecture
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
28