Item
Split-Type Air Conditioner
Indoor unit operating
humidity
5%–95% RH (non-condensing)
Storage temperature
–40°C to +70°C (without refrigerant)
–40°C to +55°C (with refrigerant)
Storage humidity
5%–95% RH (non-condensing)
Altitude
0–4000 m (derated when the altitude ranges
from 1000 m to 4000 m)
Installation Requirements
Table 3-7 Installation requirements
Item
Split-Type Air Conditioner
Installation mode
Rack-mounted
Height distance between
indoor and outdoor units
–5 m to +20 m (outdoor unit placed higher)
Maximum equivalent length of
the one-way pipe
60 m. If the length exceeds 60 m, contact the
local customer service center.
3.3.2 Technical Specifications
Table 3-8 Technical specifications
Item
Split-Type Air Conditioner
Power system
220–240 V AC, 50 Hz, 1 phase
Refrigerant
R410A
Cooling capacity
3.5 kW
a
Fan type
EC fan
Air supply mode
Front air supply and rear air return
Dimensions (H x W x D)
b
223 mm x 442 mm x 800 mm
Weight
Indoor unit: < 40 kg
Outdoor unit: < 50 kg
IP rating
Indoor unit: IP20
Outdoor unit: IPX5
FusionModule500 Smart Mini Data Center
User Manual
3 System Architecture
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
26