Context
NO TICE
● Move the outdoor unit close to the installation position before unpacking. You
are advised to keep the outdoor unit vertical during transportation. If tilt is not
avoidable, the tilt angle cannot exceed 15°.
● Do not hold the fan guard on the shell. Otherwise, it will be deformed.
● Do not touch the blades using hands or any other object.
● Remove the desiccant bound to the outdoor unit before installation.
● The outdoor unit is transported with refrigerant.
Procedure
Step 1 Determine the four mounting holes of the outdoor unit based on the installation
dimensions and drill holes in the concrete base.
Step 2 Align the outdoor unit mounting holes with the holes in the concrete base, and
secure the outdoor unit to the concrete base using four M10 expansion bolts, as
shown in
Figure 4-19 Installing an outdoor unit (unit: mm)
----End
4.2.4.6 Installing a Low-Temperature Component
Prerequisites
When the outdoor temperature is lower than –20°C, a low-temperature
component can be used to ensure normal operation at –40°C.
NO TICE
The copper pipes of the low-temperature component need to be welded, which is
different from pipe connection mode of the entire smart cooling product system.