Cate
gory
Item
2.4 MW Indoor
PowerPOD
2.0 MW Indoor
PowerPOD
1.6 MW Indoor
PowerPOD
1.2 MW Indoor
PowerPOD
2N
N+R
2N
N+R
2N
N+R
2N
N+R
ibuti
on
Input
switch/
Bus tie
switch
5000
A/3P,
3200
A/4P
5000
A/3P,
5000
A/4P
4000
A/3P,
2500
A/4P
4000
A/3P,
4000
A/4P
3200
A/3P,
2000
A/4P
3200
A/3P,
3200
A/4P
2500
A/3P,
1600
A/4P
2500
A/3P,
2500
A/4P
Reactiv
e
power
compe
nsation
500 kVar
400 kVar
300 kVar
300kVar
UPS
input/
bypass
2500 A/3P, 2000
A/3P (parameters
for a single input/
bypass cabinet,
two cabinets
required)
2000 A/3P, 2000
A/3P (parameters
for a single input/
bypass cabinet,
two cabinets
required)
3200 A/3P, 3200
A/3P
2500 A/3P, 2000
A/3P
UPS
UPS5000-H-1200
kVA x 2 PCS
UPS5000-H-1000
kVA x 2 PCS
UPS5000-H-1600
kVA x 1 PCS
UPS5000-H-1200
kVA x 1 PCS
UPS
output
2000 A/3P x 2 PCS
3200 A/3P
2000 A/3P
UPS
mainte
nance
bypass
4000 A/3P
3200 A/3P
2000 A/3P
Feeder
cabinet
Options: 160 A/250 A x 18 PCS, 400 A/630 A x 7 PCS
Mon
itori
ng
Power
and
environ
ment
monito
ring
system
ECC for centralized management
Stru
ctur
e
Externa
l
dimens
ions (H
x W x
D)
(exclud
ing the
base)
3002 mm x 12,800
mm x 1650 mm
3002 mm x 12,700
mm x 1650 mm
2475 mm x 9300
mm x 1500 mm
2475 mm x 8350
mm x 1450 mm
FusionPower6000
Product Description
3 Typical Application Scenarios and Configurations
Issue 02 (2021-06-30)