5. Access the
System Settings
>
Batt. String Config
page, and set
Batt. String Config
parameters according to the following table.
Default iBOX settings:
• IP address: 192.168.0.10
• Subnet mask: 255.255.255.0
• Gateway: 192.168.0.1
• User Name: admin
• Password: Changeme
NOTE
Batt. String Config
Description
Current acquisition
source
The actual specifications of the Hall effect sensor prevail.
Battery N line
Set whether there is a battery N wire according to the actual situation.
Single batt. group
number of HALL
Indicates the number of Hall effect sensors connected to a single
battery string.
Single batt. capacity
Specifies the capacity of each battery that is connected in the battery
string in series.
Batt. installation time
Time when the battery is installed for the first time.
iBAT number of iBOX
Indicates the total number of iBATs managed by the iBOX.
Number of battery strings
Indicates the total number of battery strings managed by the iBOX.
Batt. string No.
Sets the battery string numbers of the iBOXs connected in parallel to
unique ones when multiple iBOXs are connected in parallel.
6. Access the
System Settings
>
Running parameter
page, and set
Running parameter
parameters according to the following table.
Running parameter
Description
Parallel Communication
Configuration
This parameter needs to be set when multiple iBOXs are connected in
parallel and does not need to be set when there is only one iBOX. Set
Whether the iBOX communicates directly with the NetEco
to
Yes
,
and set
Number of iBOX configured under each UPS
. Configure IP
addresses for multiple iBOXs.
Modbus Config
Set ModbusTCP encryption and ModbusTCP authentication, which are
consistent with Connection Mode on the NetEco.
Basic Information
If a BCB box is configured, set
BCB configuration
to
Done
and
Batt.
abnormal BCB trip
to
Enable
.
HALL Rerverse Config
If the Hall effect sensor is reversely installed, you can set reverse
connection to correct it.