Logging In to the UPS WebUI and Setting Parameters
3.3
1. Use a straight-through cable to connect the PC to
the FE port on the UPS MDU.
2. Enter https://
UPS IP address
in the address box
of Internet Explorer to log in to the UPS WebUI
homepage.
MDU
3. On the UPS WebUI homepage, choose
Param. Settings
>
Battery Setting
, and set
Number of
battery strings
.
4. On the UPS WebUI homepage, choose
iBOX Settings
, and set
Basic Param.
,
Advanced
Param.
, and
Batt. String Config
.
Default UPS settings:
• IP address: 192.168.0.10
• Subnet mask: 255.255.255.0
• Gateway: 192.168.0.1
• User Name: admin
• Password: Changeme
NOTE
If the BCB box is configured, set
Batt. abnormal BCB trip
to
Enable
.
NOTE