4 Alarms and Faults
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
65
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
is insufficient, and
the UPS is shutting
down.
loads will be
powered off.
Connect the UPS input
to the backup AC
power supply
immediately.
The number of
batteries or the
battery capacity
is incorrectly
set.
Verify that the number
of batteries and
capacity are correctly
set in
Common
based
on the actual
configuration and
consistent with the
initial configuration
guide.
For other UPS2000-G alarms, see
UPS2000-G-(6kVA-20kVA) User Manual
.
4.22 35 kW Air-cooled Precision Air Conditioner Alarms
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
35 kW
air-cooled
precision
air
conditione
r alarms
Major
There is an
abnormal noise
during operation.
The
compressor,
fan, or pipes
are loose.
Check and secure
loosen parts.
Major
The compressor
does not work.
The high
pressure switch
is triggered.
Check the high pressure
switch.
The circuit
breaker, fuse,
or cable is
disconnected.
Check the main circuit
breaker, compressor
circuit breaker, fuses,
and cables.
The
compressor
motor is
damaged.
Check whether the
motor is damaged and
needs replacing.
The
compressor
does not need
to start.
Check for the
requirement status on
the LCD.