iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
236
Step 7
Click
Connection Test
to start the connection test.
Step 8
After the connection test is successful, click
in the toolbar to save the device
information.
----End
6.4.6 Adding a PDU
6.4.6.1 Setting Monitoring Parameters for a PDU8000
Prerequisites
The IP address planned for the PDU8000 is obtained.
The PDU8000 is powered on.
Context
Before connecting the PDU8000 to the NetEco, set monitoring parameters, such as
Serial
port baud rate
and
Serial port address
.
Procedure
Step 1
On the display panel of the PDU8000, press
Settings
.
Step 2
Enter the administrators password for the PDU8000, then press
.
The PDU8000 preset user name is
admin
, and the password is
000001
. To protect the access security,
change the password after logging in to the PDU8000 for the first time.
Step 3
Click
Communication
.
Set
Serial port baud rate
and
Serial port address
.
Table 6-42
Parameter description
Parameter
Description
Serial port baud rate
Indicates the baud rate. The default baud
rate is 9600. Set
BaudRate
for the collector
port to the same value.
DataBit
,
StopBit
, and
Parity
for the
PDU8000 cannot be set on the WebUI.
Their values are
8
,
1
, and
None
respectively.
Serial port address
Indicates the device address planned for the
PDU8000. The devices with the same
address cannot connect to the same port.
When creating a PDU8000 on the NetEco,
set
Device address
to the same value.