iManager NetEco 6000
Device Installation and Commissioning Guide
7 Device Maintenance
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
273
Context
Prepare a location-type water sensor or water detection cable of the same model.
The location-type water sensor consists of a water leakage locator, tieline, and water
leakage location cable. The water detection cable is laid out on the floor. The liquid level
sensor is deployed around the collector. The water detection cable and the liquid level
sensor are connected using the lead wire.
Recommended tool and material: crimping tool
Procedure
Step 1
Replace the water sensor.
1.
Pull out the water detection cable from the lead wire port on the water leakage locator.
2.
Remove the water leakage locator from the DIN guide rail.
3.
Install the new water leakage locator on the DIN guide rail with the latch facing
upwards.
Touch grounded devices or pipes to eliminate ESD before taking the water sensor module.
Place it gently. Prevent it against mechanical impact and collision. Keep it dry.
Prevent it against metal filings, grease, pipe paint, and other contaminants.
4.
Connect one end of the black quick-connect terminal of the lead wire from the liquid
level sensor to the location-type water detection cable, and connect the other end of the
quick-connect terminal to the sensor.
Step 2
Replace a water detection cable.
1.
Remove the faulty water detection cable from the port.
2.
Install a new water detection cable.
----End
Follow-up Procedure
Check whether the new location-type water sensor works properly. Connect the network cable
between the water sensor and the ECC500, immerse the water detection cable in water, and
check whether an alarm is raised. If an alarm is raised, the replacement is complete.
7.2.6 Replacing the Management System
7.2.6.1 Replacing a VCN500
Prerequisites
Recommended tools: Phillips screwdriver, flat-head screwdriver
A VCN500 needs to be replaced.
A spare VCN500 of the same model is available and functional.
Context