16
Upward water inlet pipe routing
IT Cabinet
Converged Cabinet
Converged Cabinet
IT Cabinet
Downward water inlet pipe routing
After routing water pipes, secure them to the refrigerant pipe using cable ties. If the pipes are
routed downwards, not only secure the pipes but also seal the cable hole using firestop putty.
Installing a Drainpipe
6.2
(1) Drainpipe connector: BSPT 1/2-inch, delivered with the smart
cooling product
(2) Rigid pipe conversion adapter: BSPP 1/2-inch inner screw thread
to rigid pipe connector, engineering procurement
(3) Rigid pipe: made of PP-R or other material, engineering
procurement
(4) Pagoda conversion adapter: BSPP 1/2-inch inner screw thread to
pagoda connector, engineering procurement
(5) Hose clamp, delivered with the smart cooling product
(6) Hose: made of EPDM or other material, engineering procurement
•
In upward pipe routing, install the check valve, engineering hose, and drainpipe connector by
performing steps 1–3. In downward pipe routing, install the drainpipe connector by performing step 3.
•
The drainpipe inside the indoor unit should be wrapped with the thermal insulation pipe in accessories.
•
The drainpipes must have gradients (
>
1:50), and stagnant water is not allowed.