Name
Address
DIP Switch Sequence No.
1
2
3
4
5
6
Cold aisle T/H 1
11
ON
ON
OFF
ON
OFF
OFF
Cold aisle T/H 2
12
OFF
OFF
ON
ON
OFF
OFF
Cold aisle T/H 3
13
ON
OFF
ON
ON
OFF
OFF
Hot aisle T/H 1
21
ON
OFF
ON
OFF
ON
OFF
Hot aisle T/H 2
22
OFF
ON
ON
OFF
ON
OFF
Hot aisle T/H 3
23
ON
ON
ON
OFF
ON
OFF
1. Connect the humidity and temperature (T/H) sensor cable (Silkscreen is W12.)
2. Set the sensor DIP switches
15
Turn the power switch to the position
with the same line voltage as the input
line voltage using a flat-head
screwdriver.
This step applies only to the
NetCol5000-C030H7.
The T/H sensor must be 1.5 m above
the floor. It can be secured to the
cabinet using cable ties or two M4
screws put through the holes in the
sheet metal. Then set the sensor
address based on the sensor location.
For details, see the following table.
(Optional) Setting the Power Switch
5.3
Connecting the T/H Sensor
5.4
(Optional) Teamwork Networking and Monitoring System Connection
5.5
The sensor in the fitting bag can be
installed in the aisle. Set the
sensors in the aisles corresponding
to the addresses to Enable. It is
recommended to be installed in the
cold aisle.
NOTE
5.1 Electrical Ports Introduction
describes the teamwork networking port.