Figure 4-15 Setting SNMP trap parameters
5. Tap Submit under SNMP Trap.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the main control board USB port
and successfully identified, tap Export File under MIB File to export the MIB file
to the USB flash drive for the customer's use in accessing a third-party EMS.
shows successful file export.
NO TICE
Before using a USB flash drive, ensure that its data has been scanned by antivirus
software and is secure.
Figure 4-16 Exporting the MIB file successfully
4.4.5 Correlation Relationship of Parameters
When setting parameters, pay attention to the following relationships.
Alarm Parameters
●
Supply air high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
105