Alar
m ID
Alarm
Name
Alarm
Severi
ty
Possible Cause
Solution
A281
Power
voltage
abnormal
MAJO
R
1. The power supply
voltage exceeds the
upper threshold.
2. If a voltage
jumper is used, it
may be incorrectly
connected.
3. If a toggle switch
is used, it may be
incorrectly set.
1. Measure the power
supply voltage.
2. Maintain or replace
the voltage jumper.
3. Set the toggle switch
correctly.
Power
voltage
abnormal
1. The power supply
voltage is below the
lower threshold.
2. If a voltage
jumper is used, it
may be incorrectly
connected.
3. If a toggle switch
is used, it may be
incorrectly set.
1. Check that the power
supply voltage is within
the operating range.
2. Maintain or replace
the voltage jumper.
3. Set the toggle switch
correctly.
A30C
Certificate is
about to
expire
WARNI
NG
1. The
corresponding
certificate is about
to expire.
2. The system time
is incorrectly set.
1. Apply for a new
certificate promptly and
update the existing one.
2. Calibrate the system
time.
A30D
Certificate is
not in effect
WARNI
NG
1. The installed
corresponding
certificate does not
take effect.
2. The connection of
the corresponding
certificate server is
abnormal.
3. The
corresponding
certificate is not
within the validity
period.
1. Ensure that the
certificate is correctly
installed.
2. Ensure that the
connection of the
certificate server is
normal.
3. Ensure that the
installed certificate is
within the validity
period.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
6 System Operation and Maintenance
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
144