Figure 6-14 Position of water inlet or outlet temperature sensor (NetCol5000-
C030/C032)
Step 5 Remove the waterproof connector from the sensor cable.
Step 6 Insert the spring tongue of the temperature sensor into the socket and insert the
probe of the new temperature sensor into the socket.
NO TICE
When inserting the spring tongue, keep it in close contact with the socket. Loose
contact affects the measurement accuracy.
Step 7 Reconnect the waterproof connector to the sensor cable and wrap thermal
insulation foam.
Step 8 Install the air filter. Close and lock the rear door.
----End
6.4.9 Replacing a rectifier
Prerequisites
●
The rectifier needs to be replaced.
●
A spare and functional rectifier is available.
Context
Preparation: Maintain from the rear door with power-off.
Procedure
Step 1 Tap Shutdown on the LCD home screen.