7.1.13 How to Set Alarm Parameters
Prerequisites
Before setting the alarm parameters, get familiar with the relationship among
each parameter.
Configurations of temperature and humidity alarms and main board alarms for
the air cooled devices comply with the following relationships:
●
Power underfrequency alarm threshold < Power overfrequency alarm
threshold
●
Backup power underfrequency alarm threshold < Backup power
overfrequency alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air low temperature alarm thr 5°C ≤ Return air low
temperature alarm threshold
Context
●
To set an alarm threshold, follow the instructions in this section.
●
The method for setting each alarm is the same. This section describes how to
set Threshold of Supply air high temperature alarm to 45.
●
If you need to change alarm settings, log in as the Admin user.
NO TICE
Be careful when configuring alarms. Only professional maintenance personnel can
change alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
is displayed.