Installation Requirements
Table 2-3 Installation Requirements
Item
NetCol5000-C065
NetCol5000-C030/C032
Room door
2 m high cabinet: width ≥
1.2 m, height ≥ 2.3 m. The
cabinet may topple over in
a short time.
● 2 m high cabinet: width ≥ 1.2
m, height ≥ 2.3 m. The cabinet
may topple over in a short time.
● 2.2 m high cabinet: width ≥ 1.2
m, height ≥ 2.5 m. The cabinet
may topple over in a short time.
Floor
Floor bearing capacity ≥ 530kg/m
2
Floor height ≥ 250 mm
Pipe routing
Bottom pipe routing
Cabling
mode
Top cabling
Drainage
requirements
Automatic drainage
Water supply
requirements
of wet film
The inlet water pressure should be in the range of 0.1–0.7 MPa
(A reducing valve must be installed if the inlet water pressure
exceeds 0.7 MPa.), and the temperature should be in the range
of 1°C–40°C.
The wet film humidifier should use tap water (no water
treatment facility needed for the inlet water) that meets the
following requirements:
● Non-freezing and nephelometric turbidity units (NTU): < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO
3
): ≤ 450 mg/L
Power
distribution
Leakage circuit breakers are not used for the main power route.
If leakage circuit breakers are required by the customer or by
local regulations, use the residual current circuit breakers
(RCCBs) that are not sensitive to the single-phase DC pulses and
transient current pulses.
Operating Specifications
Table 2-4 Operating specifications
Item
NetCol5000-C065
NetCol5000-C030/C032
Operating ambient
temperature
4–55°C
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)