Item
NetCol5000-C065
NetCol5000-C030/C032
Operating ambient
humidity
5%–95% RH
Inlet water temperature
of chilled water or
glycol solution
7–19°C (water, glycol solution)
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non-condensing)
Altitude
0–1000 m: normal use; 1000–4000 m: derated
Temperature
adjustment range
15–35°C
Temperature
adjustment precision
±1°C
Humidity adjustment
range
20%–80% RH
Humidity adjustment
precision
±5% RH
Air outlet static
pressure
0–50 Pa, adjustable
2.8 Technical Specifications (NetCol5000-C065)
Table 2-5 Technical specifications of NetCol5000-C065
Item
NetCol5000-C065
Power system
220 V AC to 240 V AC 1 Ph 50/60 Hz, dual
power supplies
Tolerance
Rated voltage –15% to +10%, rated frequency
±5 Hz
Number of fans
10
Cooling capacity (kW)
65
a
Air volume (m
3
/h)
10000
Maximum operating current
(A)
15
Maximum operating pressure
(MPa)
1.6
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
2 Product Description
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
25