Item
NetCol5000-C030
NetCol5000-C032
Air volume
(m
3
/h)
5400
5400
Maximum
operating
current (A)
9.5
9.5
Maximum
operating
pressure (MPa)
1.6
1.6
Humidification
● NetCol5000-C030H90D0: No
● NetCol5000-C030H9HD0: Yes
● NetCol5000-C030H9HE0: Yes
NetCol5000-C032H9HD0:
Yes
Humidification
capacity (kg/h)
● NetCol5000-C030H90D0: 0
● NetCol5000-C030H9HD0: 1.5
● NetCol5000-C030H9HE0: 1.5
NetCol5000-C032H9HD0:
1.5
External
dimensions (H
x W x D)
2000 mm × 300 mm× 1200 mm
2200 mm × 300 mm×
1200 mm
Pipe and cable
routing
Installed on the raised floor or
base. It supports underfloor
piping and overhead cabling.
Installed on the raised
floor or base. It supports
underfloor piping and
overhead cabling.
Certification
CE, RoHS, REACH, WEEE, and IEC
CE, RoHS, REACH, WEEE,
and IEC
Air filter level
G4
G4
Net weight
(kg)
● NetCol5000-C030H90D0: 162
● NetCol5000-C030H9HD0: 164
● NetCol5000-C030H9HE0: 164
NetCol5000-C032H9HD0:
175
a: Rated working conditions are that the return air temperature is 37°C; the
return air relative humidity is 24%; the supply/return water temperatures are
10°C/15°C respectively; and the static pressure outside the smart cooling
product is 0 Pa.
2.10 Performance Curves
show the cooling capacity derating coefficient curve
in proportion to the altitude when the NetCol5000-C works under rated power
and air flow.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
2 Product Description
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
27