Figure 3-6 Pipe supports (unit: mm)
NO TE
● The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including
the thermal insulation foam).
● Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away
from each bending point in turning sections.
3.1.3.5 Cables
NO TICE
The cable flame spread rating must be at least VB.
The following lists the cables and devices to be connected. When connecting
cables, fit them with protective hoses.
Table 3-4 Cables and switches required (NetCol5000-C065)
Name
Specifications
Quanti
ty
Remarks
Power
cable
Electronic|Electric Cable, 600 V/
1000 V, ZA-RVV, 3 x 6 mm
2
, Black
(3 Cores: Brown, Blue, Yellow/
Green), 46 A, Outdoor Cable, CE
2 PCS
Optional; same
cable parameters
for the active and
standby routes
Teamwork
networkin
g and
monitoring
cable
Signal cable, shielded straight-
through cable, 10 m, MP8-II,
CC4P0.5GY (S), MP8-II, FTP
1 PCS
Optional
Fuse
Slow Blow Fuse, 500 V, 3.15 A
2 PCS
Standard
configuration;
delivered with the
product
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
35