Figure 3-58 Cables routed outside the cabinet (NetCol5000-C030/C032)
NO TE
● The T/H sensors should be 1.5 m above the ground (33 U).
● Each smart cooling product supports a maximum of ten T/H sensors.
Step 2
shows how to set the DIP switches for T/H sensors.
Table 3-6 DIP switch setting on a T/H sensor
Positi
on
Name
Addr
ess
DIP Switch ID
1
2
3
4
5
6
Cold
aisle
Cold aisle 1
temp/humid
11
ON
ON
OFF
ON
OFF
OFF
Cold aisle 2
temp/humid
12
OFF
OFF
ON
ON
OFF
OFF
Cold aisle 3
temp/humid
13
ON
OFF
ON
ON
OFF
OFF
Cold aisle 4
temp/humid
14
OFF
ON
ON
ON
OFF
OFF
Cold aisle 5
temp/humid
15
ON
ON
ON
ON
OFF
OFF
Hot
aisle
Hot aisle 1
temp/humid
21
ON
OFF
ON
OFF
ON
OFF
Hot aisle 2
temp/humid
22
OFF
ON
ON
OFF
ON
OFF
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
74