Menu
Parameter
Description
Configuration Principle
Hot aisle sensor 1–
5
Hot aisle sensors
can be set to
Enable or
Disable.
If a T/H sensor outside the
cabinet is deployed in the
hot aisle, enable the T/H
sensor.
Cold aisle
temperature and
humidity sharing
When this
parameter is
enabled, the
smart cooling
product, which is
not configured
with the cold
aisle T/H sensor
in the group, is
logically
controlled by
using the
acquired value
of the
configured cold
aisle T/H sensor.
Disable
Hot aisle
temperature and
humidity sharing
When this
parameter is
enabled, the
smart cooling
product, which is
not configured
with the hot
aisle T/H sensor
in the group, is
logically
controlled by
using the
acquired value
of the
configured hot
aisle T/H sensor.
Disable
System
Settings
Dual power supply
setting
Primary power
first, or Primary
power first can
be set as
required.
Retain the default value.
Altitude
Set the
parameter
according to the
actual situation.
-
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.