Menu
Parameter
Description
Configuration Principle
In-cabinet water
overflow alarm
action
Based on site,
set the device
action to
Shutdown,
Inactivity, Only
indoor fan
running, or
Humidification
stopped after
the floor
overflows.
Retain the default value.
T/H
sensor
Temperature and
humidity control
type
Cold aisle, Hot
aisle, Return
air, or Supply
air can be set as
required. The
temperature and
humidity set
points
correspond to
the selected
control type can
be set.
● When the application
scenario is cold or hot
aisle containment, you
are advised to choose
Cold aisle if the cold
aisle T/H sensors are
configured, and choose
Supply air if the cold
aisle T/H sensors are
not configured.
● When the application
scenario is non-aisle
containment, you are
advised to choose
Return air, and choose
Cold aisle if the cold
aisle T/H sensors are
configured.
● Hot aisle is not
recommended.
Temperature
setpoint
After the
Temperature and
humidity control
type and the
temperature
value under this
type are set, the
device conducts
cooling or
heating based
on the settings.
Set this parameter as
required.
● Return air temperature:
26–35°C recommended
● Supply air temperature:
18–24°C recommended
● Cold aisle temperature:
18–24°C recommended
● Hot aisle temperature:
26–35°C recommended
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)