Menu
Parameter
Description
Configuration Principle
Humidity setpoint
After the
Temperature and
humidity control
type and the
humidity value
under this type
are set, the
device conducts
humidifying or
dehumidifying
based on the
settings.
Set this parameter as
required.
40%–60% RH
recommended
Comm
Settings
Modbus Comm
address
Set the
communication
address of the
smart cooling
product as
planned. The
EMS
communicates
with the smart
cooling product
through this
address.
The communication
addresses of two smart
cooling products
connecting to the same
EMS must be unique.
----End
4.2 Home Screen
You can tap the menu items, buttons, or icons on the screen to enter related
screens or perform operations, such as Running, Alarms, and Settings. The
controller main screen is shown in
.
NO TICE
User interfaces displayed in this document are for reference only.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
4 Commissioning
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
85