Figure 4-5 Cold aisle temperature and humidity
----End
4.4.2 (Optional) Setting the Pressure Difference Control
Prerequisites
If the differential pressure sensor is installed, perform the following operations
accordingly. If the differential pressure sensor is not installed, skip this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-
side difference pressure sensor type to 0~50 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Table 4-5 Parameter description
Parameter
Description
Configuration Principle
Indoor fan control type
Sets the control type for
the indoor fan.
Normally, retain R/S air
temp diff rate ctrl. If
the differential pressure
sensors are configured,
change to Pressure diff
ctrl.
Indoor fan silent mode
Set maximum speed of
indoor fan to reduce
equipment noise.
You are advised not to
change the value.
Indoor fan pressure
difference setpoint
Sets the value for the
pressure difference
control.
The default value is 10
Pa. When there are
partial hot spots indoors,
you are advised to raise
the value to ensure that
the air volume of the
indoor fans is between
60%–70%.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)