NO TE
For the NetCol5000-C030/C032, remove the butterfly nut and sheet metal fastener.
Step 4 Remove the hose clamp and remove the water inlet pipe.
Step 5 Draw out the old wet film humidifier.
Step 6 Install the new wet film humidifier by performing
.
NO TICE
After the replacement is complete, properly install the water inlet pipes to the wet
film humidifier. Ensure that the water inlet pipes are secured without leakage
risks.
Step 7 Open the rear door, installation the air filter, and Turn on the switches.
Step 8 Choose Maint > Performance Maint on the home screen to access the
Performance Maint screen. Then clear the humidifier runtime.
Step 9 Choose Settings > System Settings > System Control > Humid > Action.
----End
6.4.5 Replacing the Differential Pressure Switch
Prerequisites
●
The differential pressure switch needs to be replaced.
●
A spare differential pressure switch of the same model is available and
functional.
Context
Tool: Phillips screwdriver
Procedure
Step 1 Tap Shutdown on the LCD home screen.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
LCD.
Step 2 Open the rear door, remove the air filter, and switch off general circuit breakers.
Step 3 Remove the pressure inlet tube from the differential pressure switch, use a Phillips
screwdriver to remove the four screws from the switch, and take out the switch.
Step 4 Remove the screws from the differential pressure switch cover, and remove the
cable.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
6 System Operation and Maintenance
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
152