Figure 3-52 Connecting the FE teamwork network cable (NetCol5000-C030/C032)
----End
3.12.4.3.2 Connecting the CAN Teamwork Cable
Context
In CAN networking, one teamwork network supports a maximum of 32 smart
cooling products. If CAN networking is required onsite, set Teamwork CAN
resistor enable on the Teamwork settings page for the first and last smart
cooling products to Yes.
Procedure
Step 1 Prepare the 8pin standard network cable, the cable pin sequence requirements are
shown below.
Figure 3-53 CAN_IN/CAN_OUT network cable pin sequence
Step 2 Use a CAN teamwork cable to connect the CAN_OUT port on a smart cooling
product to the CAN_IN port on the following smart cooling product, as shown in
.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
70