5.4.6 Setting Communications Parameters (SNMP Settings)
Context
●
To set communications parameters, log in as the Admin or Engineer user.
●
This section is suitable only for SNMP. Skip this section if you use Modbus.
●
Record the values entered in this section. They will be used when you access a
smart cooling product to an EMS (element management system).
●
One smart cooling product supports concurrent access of up to 10 EMSs
through SNMP.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
is displayed.
Figure 5-9 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
●
If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read
Community and Write Community. You can modify the settings by following
instructions provided in
●
If you set SNMP Version to ALL or SNMPv3, you can add SNMPv3 users by
performing
Step 3 Set Read Community and Write Community.
1. Tap the text box after Read Community, as shown in
. Set Read
Community as planned, tap
, and then tap Submit.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
101