Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1. Tap Add under SNMP Trap.
2. Set Trap Address as planned and Trap Port to the actual port number.
NO TE
Trap Port is set to 162 by default.
3. Select the SNMP Version. If an SNMPv3 user is configured, it is recommended
that SNMP Version be set to SNMPv3.
4. If SNMP Version is set to SNMPv3, select an SNMPv3 user name, and then
tap
, as shown in
Figure 5-17 Setting SNMP trap parameters
5. Tap Submit under SNMP Trap.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the controller USB port and
successfully identified, tap Export File under MIB File to export the MIB file to the
USB flash drive for the customer's use in accessing a third-party EMS.
shows successful file export.
NO TICE
Before using a USB flash drive, ensure that its data has been scanned by antivirus
software and is secure.