Table 5-6 Teamwork settings
Paramete
r
Description
Configuration
Principle
Default Value
Teamwor
k group
no.
The number of the
teamwork controlled
group, which is the
same for all the
devices in the group.
Set the assigned
teamwork control
number.
1
Teamwor
k unit
address
Only one device in
each group can be
set to 1. Other
device addresses
should be different
from each other.
Set the assigned unit
address.
NA
Teamwor
k CAN
resistor
enable
Indicates the build-
out resistor status of
each smart cooling
product in a
teamwork group.
● Set this
parameter to No
for non-
teamwork
scenarios.
● For teamwork
scenarios, set this
parameter to Yes
for the first and
last smart cooling
products in a
teamwork group,
and set it to No
for other smart
cooling products.
No
Teamwor
k function
Disable or enable
the teamwork
function. If the
teamwork function
is disabled, this
device is operating
according to its own
control If the
teamwork function
is enabled, this
device works in
harmony with others
that in the same
group.
Set this parameter
based on the onsite
device heat
distribution.
Disable
Teamwor
k mode
Smart
N/A
Smart
Network
Networking mode
for the teamwork.
Networked over
CAN.
CAN
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
107