Figure 5-42 Sensor adjust screen
Step 2 Fill the calibration value based on the measured error.
----End
5.7.6 Calibrating the Screen
Context
●
You can calibrate for touching point deviation on the touchscreen.
●
You can calibrate the screen by tapping the screen on the Screen Calib page
or by DIP switch.
–
Tapping the screen on the screen calib page: The program of the display
board works normally; the deviation between the touching point and the
responding point is small; the Maint > Screen Calib page can be entered
over the screen.
–
Calibrating the screen by DIP switch: The display board works normally;
the deviation between the touching point and the responding point is
unfavorably big; or the screen does not respond when being tapped.
●
To calibrate the touchscreen, log in as the Admin or Engineer user.
NO TICE
● You can calibrate the screen by DIP switch only when the system enters Quick
Settings page after the first power-on or when the system is on the home
screen.
● Touch the LCD screen firmly if you are using your fingertips. It is recommended
that you use the pen tip for accurate selection and quick response.
Procedure
●
When calibrating the screen by tapping the screen, on the home screen, tap
Maint > Screen Calib to enter the following screen, as shown in
is displayed when the screen calibration is complete.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual