Figure 7-23 Replacing a water supply valve
(1) Nut of the water inlet pipe (2) Connection nut
(3) Water supply valve
Step 4 Perform
in reverse order to reinstall the new water supply valve.
Step 5 Power on the equipment. On the main screen, choose Maint > Diagnostic Mode
> Enter, on the main menu, open the water supply valve and humidifier, and
check that the humidifier works properly. Then exit from the diagnostic mode.
----End
7.4.5 Replacing Electrical Heaters
Context
NO TICE
● Prevent bolts from falling into the fan when you loosen the bolts on the
electrical heater rack.
● Hold the electrical heater rack with hands while moving it to prevent the rack
from falling to the bottom of the NetCol8000-A when the rack is out of
position.
● The electrical heater rack is inside the NetCol8000-A. Exercise caution during
maintenance to prevent internal components from scratches or damage.
Procedure
Step 1 Disconnect the power supply.
Step 2 Disconnect the cables from the electrical heater.