Pipe Outer
Diameter
(in)
45-degree
Bends
90-degree
Bends
180-degree
Bends
T-Junction
7/8
0.24 m
0.42 m
0.8 m
1.2 m
1
0.28 m
0.5 m
1 m
1.3 m
1-1/8
0.32 m
0.6 m
1.2 m
1.4 m
3. The total length of pipes connecting the indoor unit and the outdoor unit
equals to the equivalent length for the local resistance loss plus the length of
the straight pipes connecting the indoor unit and the outdoor unit.
4. You are advised to select the pipes based on the total length of the pipes
connecting the indoor unit and the outdoor unit, because different pipe
diameters influence the pressure drop and performance of the cooling system.
.
Table 3-11 Recommended pipe specifications
Pipe Length (m)
Recommended
Diameter for Discharge
pipe (in)
Recommended
Diameter for Liquid
Pipes (in)
L ≤ 30
7/8
5/8
30 < L ≤ 60
1
3/4
NO TE
If the pipe is longer than 60 m, contact Huawei.
The refrigerant pipes connecting the indoor unit and the outdoor unit are copper.
Ball valves are reserved for the discharge pipes and liquid pipes.
shows the specifications and positions of the ball valves. Before welding, open the
ball valve bonnet using an adjustable wrench and switch the ball valve to a
direction parallel with the copper pipe to ensure that it is fully open.