3.6.5.2 Connecting Outdoor Unit On/Off Signal Cable
Route the signal cables through the cable protecting ring on the bottom of the
cabinet, through the lower cable hole on the cabinet and along the left of the
cabinet. Fix the cables with cable ties.
3.6.5.2.1 Connecting NetCol500-A072
●
One indoor unit connects to two outdoor units when connecting NetCol8000-
A100 smart cooling product. Indoor unit control ports 1A/1B respectively
connect to port 1 and port 2 of outdoor unit No. 1. Indoor unit control ports
2A/2B respectively connect to the port 1 and port 2 of outdoor unit No. 2.
●
One indoor unit connects to one outdoor unit when connecting NetCol8000-
A050 smart cooling product. Control ports 1A/1B of the indoor unit
respectively connect to port 1 and port 2 of outdoor unit.
3.6.5.2.2 Connecting NetCol500-A088
●
One indoor unit connects to two outdoor units when connecting NetCol8000-
A100 smart cooling product.
–
Control ports 1A and 1B of the indoor unit connect to port 1A/2A and
port 1B/2B of the No. 1 outdoor unit respectively.
–
Control ports 2A and 2B of the indoor unit connect to port 1A/2A and
port 1B/2B of the No. 2 outdoor unit respectively.
●
One indoor unit connects to one outdoor unit when connecting NetCol8000-
A050 smart cooling product. Control ports 1A and 1B of the indoor unit
connect to port 1A/2A and port 1B/2B of the outdoor unit respectively.
3.6.5.3 Connecting a Water Sensor (Optional)
Context
A water sensor monitors resistance changes at terminals to check whether the
floor is watery. The resistance at the terminals becomes small if the terminals
detect water or any other conductive liquid. Keep the sensor far away from drain
traps or floor drains.
Procedure
Step 1 Connect one end of the water sensor cable to the water sensor.
Step 2 Connect the other end of the signal cables to terminals 38 and 39 on the electrical
control box.
Step 3 Use a cable tie to fix the cables on the cabinet.
----End
3.6.6 Teamwork Networking and Monitoring
Context
Teamwork communication ports 1 and 2 are used to enable the teamwork
networking communication over CAN and EMS monitoring communication over
NetCol8000-A(050, 100) In-room Air Cooled Smart