fans." message is displayed. Then tap Yes. The command is triggered successfully
and the alarm is cleared.
Step 11 On the home screen, choose Maint > Diagnostic Mode > Enter. On the displayed
screen, increase the indoor fan speed to check that the fan speed is normal. Check
that it works properly before you exit.
Step 12 Install the fan maintenance baffle and close the front door.
Step 13 On the home screen, choose Maint > Performance Maint to enter the
Performance Maint screen and clear the runtime of the indoor fan.
----End
11.9.2 Replacing an Indoor Fan (NetCol8000-A060U)
Context
Recommended tools and materials: 13# socket wrench and Phillips screwdriver
CA UTION
Exercise caution during replacement as the fan is heavy.
NO TICE
Two persons are required to move a fan.
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the front door and turn off the general switch. Then, remove the fan
maintenance cover using a Phillips screwdriver.
Step 3 Disconnect the fan cable from the plug-in terminals reserved in the cabinet.
Step 4 Remove the four M4 screws using a Phillips screwdriver, and rotate the buckle
outwards. The bottom fixing plate of the fan tilts downward.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
11 Parts Replacement
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
275