25
Model Config
uration
Power
system
Maximum
Current (with
Heating and
Humidificatio
n/Without
Heating or
Humidificatio
n)
Recommended
Switch (with
Heating and
Humidification/
Without Heating
or
Humidification)
Cable Diameter
(with Heating and
Humidification/
Without Heating
or
Humidification)
Dimension
s (H x W x
D, mm)
8000-C
100
route
0V AC,
3PH,
50/60H
z
x 1000
(double-door
)
Dual
route
380–41
5V AC,
3PH,
50/60H
z
Active:
30.4A/9.4A
Standby: 9.4A
Active: C40/C25
Standby: C25
Active: 4 x 6mm
2
/4
x 4mm
2
Standby: 4 x 4mm
2
NetCol
8000-C
110
Single
route
380–48
0V AC,
3PH,
50/60H
z
29.9A/8.9A
C40/C25
4 x 6mm
2
/4 x 4mm
2
Dual
route
380–41
5V AC,
3PH,
50/60H
z
Active:
29.9A/8.9A
Standby: 8.9A
Active: C40/C25
Standby: C25
Active: 4 x 6mm
2
/4
x 4mm
2
Standby: 4 x 4mm
2
NetCol
8000-C
130
Single
route
380–48
0V AC,
3PH,
50/60H
z
29.9A/8.9A
C40/C25
4 x 6mm
2
/4 x 4mm
2
Dual
route
380–41
5V AC,
3PH,
50/60H
z
Active:
29.9A/8.9A
Standby: 8.9A
Active: C40/C25
Standby: C25
Active: 4 x 6mm
2
/4
x 4mm
2
Standby: 4 x 4mm
2
NetCol
8000-C
150
Single
route
380–48
0V AC,
3PH,
50/60H
z
34.8A/13.8A
C40/C25
4 x 6mm
2
/4 x 4mm
2
2000 x 2700
x 1000
(triple-door)
Dual
route
380–41
5V AC,
3PH,
50/60H
z
Active:
34.8A/13.8A
Standby: 13.8A
Active: C40/C25
Standby: C25
Active: 4 x 6mm
2
/4
x 4mm
2
Standby: 4 x 4mm
2
NetCol
Single
380–48
34.1A/13.1A
C40/C25
4 x 6mm
2
/4 x 4mm
2