4 Commissioning
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
139
If
Link mode
is
Server
, a smart cooling product can be accessed by element
management system (EMS) client. If
Link mode
is
Client
, a smart cooling product can
be connected only to the EMS with the corresponding IP address. If
Link mode
is
Server and client
, a smart cooling product can be accessed by EMS client and connect
to the EMS with the corresponding IP address at the same time.
Procedure
Step 1
On the home screen, choose
Settings
>
Comm Settings
>
IP Settings
.
Step 2
Set the parameters by referring to
Table 4-9
IP parameter settings
Parameter
Setting Method
IP assigning
mode
Set according to the actual plan.
IP address
Set according to the actual plan.
Subnet mask
Set according to the actual plan.
Gateway
Set according to the actual plan.
Step 3
Tap
Submit
.
Step 4
On the home screen, choose
Settings
>
Comm Settings
>
Modbus Settings
.
Step 5
Set parameters for Modbus TCP by following instructions.
Table 4-10
Modbus TCP parameter settings
Parameter
Setting
Setting Method
Link mode
Server, Client,
Server and
client
If you set
Link mode
to
Server
, the smart cooling
product, as a server, supports two client connection
and establishes communication.
If you set
Link mode
to
Client
, the smart cooling
product, as a client, can connect to a remote server and
establish communication.
If you set
Link mode
to
Server and client
, the smart
cooling product, as a server, supports two client
connection and establishes communication. In
addition, the smart cooling product, as a client, can
connect to a remote server and establish
communication.
Client
encryption
Enable,
Disable
This parameter is configurable when
Link mode
is set to
Client
.
Server
encryption
Enable,
Disable
This parameter is configurable when
Link mode
is set to
Server
.
NMS IP
N/A
Enter the actual IP address of the EMS. IP addresses of