Step 6 Power on the device and tap Startup on the home screen. Ensure that the device is
running normally without any alarms.
----End
6.5.14 Replacing the T/H Sensor
Prerequisites
●
The T/H sensor needs to be replaced.
●
A spare T/H sensor of the same model is available and functional.
●
Tool: Phillips screwdriver, scissors
●
The equipment has two T/H sensors, located on the outdoor air inlet side and
return air side. This chapter takes the replacement of the outdoor air intake
T/H sensor as an example to introduce the replacement method.
Procedure
Step 1 Tap Shutdown on the controller home screen.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Remove the air filter of outdoor air intake side port.
Step 3 Disconnect the cable from the T/H sensor.
Step 4 Slide and remove the T/H sensor.
Step 5 Install a new T/H sensor and reconnect the cable.
Step 6 Power on the device and tap Startup on the home screen. Ensure that the device is
running normally without any alarms.
----End