Default Value
Hot aisle low
temperature
alarm
Specifies the alarm
threshold for a certain
alarm.
15.0 ºC
High humidity
alarm
Specifies the alarm
threshold for a certain
alarm.
85.0 %RH
Low humidity
alarm
Specifies the alarm
threshold for a certain
alarm.
10.0 %RH
Settings >
Alarm
Settings >
Mainboard
Return air filter
blocked alarm
● Enable: Alarms are
reported to the EMS.
The LCD displays active
alarms and the system
implements related
protection actions.
● Disable: Alarms are not
reported and no
protection actions are
implemented.
Enable
Power phase
sequence
abnormal
● Enable: Alarms are
reported to the EMS.
The LCD displays active
alarms and the system
implements related
protection actions.
● Disable: Alarms are not
reported and no
protection actions are
implemented.
Enable
Primary power
failure alarm
● Enable: Alarms are
reported to the EMS.
The LCD displays active
alarms and the system
implements related
protection actions.
● Disable: Alarms are not
reported and no
protection actions are
implemented.
Enable