![background image](http://html.mh-extra.com/html/huawei/netcol8000-e220/netcol8000-e220_user-manual_22074269.webp)
Menu
Name
Description
Default Value
System power
limit
Specifies the maximum
power of the equipment.
CAUTION
The value of System power
limit is related to the overall
design solution. Do not
change the value unless
necessary. If System power
limit is set to an incorrect
value, the upstream power
supply may be abnormal.
74.0kW
Settings >
System
Settings >
T/H sensor
Temperature and
humidity control
type
Cold aisle, Hot aisle,
Return air, or Supply air
can be set as required. The
temperature and humidity
set points correspond to
the selected control type
can be set.
Supply air
Temperature
control mode
Controls the temperature
inside the room or aisles
based on the Average
valve, Max valve, or Min
valve of the temperatures
collected by each sensor.
Average value
Temperature
setpoint
After the Temperature and
humidity control type and
the temperature value
under this type are set, the
device conducts cooling or
heating based on the
settings.
22.0 ºC
Humidity
setpoint
After the Temperature and
humidity control type and
the humidity value under
this type are set, the device
conducts humidifying or
dehumidifying based on
the settings.
50.0 %RH
Cold aisle sensor
The sensors in cold aisles
can be set to Enable or
Disable.
Disable
Hot aisle sensor
The sensors in hot aisles
can be set to Enable or
Disable.
Disable
Settings >
System
Collaborative
working mode
Choose between
Alternative and
Synchronized control.
Alternative
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
260