Menu
Name
Description
Default Value
Temperature
setpoint
After the Temperature and
humidity control type and
the temperature value
under this type are set, the
device conducts cooling or
heating based on the
settings.
22.0 ºC
Humidity
setpoint
After the Temperature and
humidity control type and
the humidity value under
this type are set, the device
conducts humidifying or
dehumidifying based on
the settings.
50.0 %RH
Cold aisle sensor
The sensors in cold aisles
can be set to Enable or
Disable.
Disable
Hot aisle sensor
The sensors in hot aisles
can be set to Enable or
Disable.
Disable
Settings >
Quick
Settings >
Comm
Setting
Modbus Comm
address
Set the communication
address of the smart
cooling product as
planned. The EMS
communicates with the
smart cooling product
through this address, and
the communication
addresses of two smart
cooling products
connecting to the same
EMS must be unique.
1
Maint >
Performance
Maint
Indoor fan total
runtime
Total runtime for each
component.
0 h
Return air filter
total runtime
0 h
Outdoor intake
air filter total
running time
0 h
Compressor total
runtime
0 h
EEV total
runtime
0 h
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
264