![background image](http://html.mh-extra.com/html/huawei/netcol8000-e220/netcol8000-e220_user-manual_22074031.webp)
Item
Parameter
Storage humidity
5%–95% RH
Protection level
IPX5 (indoor)
Installation mode
The concrete foundation or steel base is required.
Altitude
Not derated below 1000 m; derated when the
altitude is between 1000 m and 4000 m. For details
about derating, see
.
Table 2-7 Altitude derating coefficients
Altitude
(m)
0
1000
1500
2000
2500
3000
3500
4000
Air volume
coefficient
1
0.887
0.835
0.785
0.737
0.692
0.649
0.608
Cooling
capacity
coefficient
1
0.887
0.835
0.785
0.737
0.692
0.649
0.608
Note: The sensible heat ratio is always 100%.
Installation Requirements
NO TICE
If the total actual load of servers for each smart cooling product is less than 10%
of rated cooling capacity or the equipment room is not properly sealed, the
humidity in the equipment room may exceed the upper limit. This is not a product
quality issue and you are advised to add a dehumidifier.
Table 2-8 Installation requirements
Name
Parameter
Base
Bearing capacity ≥ 500 kg/m
2
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
2 Product Description
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
22