Name
Connector
Pipe
Dimensions
Material
Quantit
y
Length
Condensa
te
drainpipe
G 3/4 inch
port with
inner screw
threads
DN20
Rigid pipe:
made of PP-
R, C-PVC, or
other
materials
2
3.2.3 Pipe Support
Supports for pipes and water pipes as shown in the figure. The actual appearance
of the supports will be different based on onsite situations.
Figure 3-4 Pipe supports (unit: mm)
NO TE
● The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including
the thermal insulation foam).
● Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away
from each bending point in turning sections.
3.2.4 Cable
NO TICE
Waterproof connectors are designed based on the cable specifications
recommended in the table. If the cables used onsite are inconsistent with the
recommended specifications, the cables may fail to pass through waterproof
connectors or the waterproof connectors cannot be locked.