----End
Follow-up Procedure
Use the multimeter to check each component and ensure that the ground resistance of each
component is smaller than 1 ohm.
6.22 Connecting Power Cables
The N8500 only supports AC power. You only need to connect AC power cables before
powering on the N8500.
Prerequisites
The N8500 has been disconnected from all external power sources.
The maximum peak power of each component is as follows:
l
clustered NAS engine enclosure: 830 W
l
SUC: 539 W
l
Storage unit disk enclosure (2 U): 300 W
l
Storage unit disk enclosure (4 U): 550 W
l
Fibre Channel switch: 90 W
l
Ethernet switch: 63 W
OceanStor N8500 Clustered NAS Storage System
Installation Guide (for T Series V100R005)
6 N8500 Installation (with S5500T Storage System as the
Storage Unit)
Issue 02 (2015-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
146