Figure 13-1
Cable bundling
1: Wrong place of the
cable tie (at turning)
2: Correct place of the cable ties 3: Loose bundling of the
cable tie
4: Burr of the cable tie
(not trimmed off)
5. Correct trimming of the
cable tie
6: Recommended span between
two cable ties
13.2 Fiber Cabling and Bundling
This section describes the method of and requirements on fiber routing and bundling.
13.2.1 Fiber Routing
This section describes the method of and requirements on fiber routing.
l
During the hardware installation, cut the corrugated pipe according to the actual required
length. The cut of the corrugated pipe is so sharp that it will wear the fiber. Wrap it with
adhesive tape to protect the fiber.
l
Forcible pulling and unnatural bending are not allowed in the fiber routing. There should
be no other cables on the fibers.
l
The bending radius of fibers cannot be less than 5 cm.
l
For fibers inside the cabinet, route them along cabinet post on the sides and bundle them
on the post when necessary.