NOTICE
l
When peeling off the insulation layer of the power cable, ensure that the conductor of the
power cable is not scratched.
l
You can adjust L1 according to the length of the ring terminal. L1 = L + (1 or 2) mm.
Table 14-3
Mapping between the cross-sectional area and the length of the insulation layer to
be peeled off (L1)
Cross-Sectional Area (mm
2
)
L1 (mm)
1
7
1.5
7
2.5
7
4
8
6
9
10
11
16
13
25
14
35
16
50
16
NOTE
Skilled engineers can determine the length of insulation layer to be peeled off by comparing the cable with
the connector to be crimped.
Step 2
Insert the power cable into the heat shrink tube A, as shown in
.
Step 3
Insert the bare conductor of the power cable into the ring terminal B, and then press the ring
terminal close to the insulation layer C, as shown in
.
OceanStor N8500 Clustered NAS Storage System
Installation Guide (for T Series V100R005)
14 Making Cables and Connectors
Issue 02 (2015-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
320