2
Appearance
PDC is short for power distribution cabinet.
PDU is short for power distribution unit.
UPS is short for uninterruptible power system.
PDU Model
PDC-0038V4ACIOA-V2
Applicable UPS
UPS2000-G-3KRTL/6KRTL-V2
Weight
15 kg
Dimensions
(H x W x D)
130 mm x 430 mm x 585 mm
1
2
3
4
5
6
7
8
1. UPS 1 mains input
circuit breaker
2. UPS 2 mains input circuit
breaker
3. UPS 1 bypass input circuit
breaker
4. UPS 2 bypass input circuit
breaker
5. UPS 1 output circuit
breaker
6. UPS 2 output circuit
breaker
7. Maintenance bypass circuit
breaker
8. Maintenance bypass circuit
breaker cover
PDC-0038V4ACIOA-V2
Front panel (under the cover)
Rear panel
1
2
4
5
6
7
3
8
9
10
11
12
13
14
15
16
1. Maintenance bypass
ports
2. Dual in-line package (DIP)
switch
3. Control area network (CAN)
communications ports
4. Output ports
5. Bypass input ports
6. Mains input ports
7. Output socket group 1 (250 V
AC, 15 A, disabled in the case
of 110 V output)
8. Output socket group 1
fuses (250 V AC, 15 A)
9. Output socket group 2
fuses (250 V AC, 10 A)
10. Output socket group 2
(250 V AC, 10 A, disabled in
the case of 110 V output)
11. UPS 1 mains input port
12. UPS 2 mains input port
13. UPS 1 bypass input
port
14. UPS 2 bypass input port
15. UPS 1 output port
16. UPS 2 output port