Figure B-2
Internal partition wall inside the equipment room
B.1.4 Requirements for Temperature, Humidity, and Altitude
Ensure suitable temperature and humidity in the equipment room. Ensure that the altitude of the
equipment room is lower than the equipment requirement.
gives the specific
requirements.
Table B-2
Requirements for temperature, humidity, and altitude
Item
Requirements
Temperature
Long-term
operation
0°C (32°F) to 40°C (104°F)
Short-term
operation
-5°C (23°F) to +50°C (122°F)
Storage
-40°C (-40°F) to +70°C (158°F)
Relative
humidity
Long-term
operation
5% RH to 85% RH
Short-term
operation
0% to 95%
Storage
0% to 95%
Long-term altitude
Less than 3,000 m (9842.4 ft)
Storage altitude
Less than 5,000 m (16404 ft)
HUAWEI NetEngine80E Router
Installation Guide
B Environmental Requirements for Device Operation
Issue 02 (2011-09-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
116