Distance from the PDF to
the Device
Cables and Terminals
Wire,450/750V,60227 IEC
02(RV)25mm^2,black,110A
Each power module should
be equipped with three cables
of this type. The cable length
is determined by the project
survey on site.
Naked Crimping
Terminal,OT,
25mm^2,M6,Tin
Plating,Width Less Than
12.4mm,For OEM
Each cable should be
equipped with one terminal
of this type.
Naked Crimping
Terminal,OT,
25mm^2,M8,Tin
Plating,Naked Ring
Terminal
Each cable should be
equipped with one terminal
of this type.
Longer than 35 m
A PDF should be placed near the device.
Formula calculating cable
cross-sectional area
S = ( I * L ) / 74
S: indicates cross-sectional area.
I: indicates the current flowing through the cable.
L: indicates distance from the PDF to the device
E.1.2 Guide to the DC Power Distribution (8KW)
Guide to the DC power distribution (8KW)
Specifications of the DC Power Module NEPS8000-D
shows the appearance of DC power module NEPS8000-D (8 KW).
Figure E-3
Appearance of the DC power module NEPS8000-D (8 KW)
HUAWEI NetEngine80E Router
Installation Guide
E Guide to Power Distribution Design
Issue 02 (2011-09-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
155